Transport Package: | Boxes |
---|---|
Specification: | 262mm× 165mm× 35mm |
Trademark: | FLEXEM |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Hardware Parameter | CPU | 300MHz ARM9 |
Memory | 128M Flash + 64M DDR2 | |
Digital Input | 6-line DI input for liquid level floating ball and door contact. | |
Digital Output | 6-line relay output (220V/5A) | |
Analog Input | 5-line 4-20mA input for connecting water quality monitoring sensor. | |
Mutual Inductor | 4-line mutual inductor input and inductor shall be installed Outside. |
|
Communication Ports | 2-line RS485 used for current gauge connection | |
Wireless Communication | 4G | |
Ethernet Ports | 1-line Ethernet port used for connecting network devices or Ethernet. | |
Backup Battery | It supports alarming during powering off. | |
Position | Base station position | |
Timer | Available | |
Programming | PLC ladder diagram programming | |
Local Storage | Over 5000 historical data | |
Remote Upgrading | Remote program upgrading, and remote data equipping | |
3rd part Connection | HTTP/SDK connection ports, MQTT | |
Electrical Specifications |
Power Consumption | < 8W |
Input Power | AC220V(100V~250V) | |
Power Protection | Protected from thunderstrike and surging | |
Power Down Allowed | < 500mS | |
CE & RoHS | Complied with EN61000-6-2:2005, EN61000-6-4:2007, ROHS, Surge Immunity:±1KV, EFT:±2KV,ESD:4KV, Air:8KV | |
Environmental Requirements |
Operating Temperature | -20~70C |
Storage Temperature | -30~80C | |
Anti-UV | Prohibit working in strong UV environment(Such as direct sunlight) | |
Operating Humidity | 10~90%RH (No Condensate) | |
Vibration Endurance | 10~25Hz (X,Y,Z direction 2G/30 minutes) | |
Mechanical Index |
Degree of Protection | Back frame confirms to IP54 |
Mechanical Structure | Metal | |
Dimension | 262mm×165mm×35mm | |
Weight | About 1000g |