Input Characteristics | 4 Point Bipolar |
Rated Voltage | 24 VDC |
Input Range | 0~28.8V DC |
Rated Current | 7mA |
Voltage Peak Value | 30V |
Current | 9mA |
Voltage in State 1 | >15V 15~28.8V |
Voltage in State 0 | <5V 0~5V |
Currentin State 1 | >2.5mA |
Currentin State 0 | <1.0mA |
Isolation | ptocoupler |
Input Impedance | 3.3KQ |
Filter Time | Default 1ms,16 equally divided levels selectable from unfiltered to 100ms |
Compatibility | Compatible with 2/3 wire sensors |
Input Type | Source/sinking |
Cable Length and Type | Max 100m shielded cable,50m unshielded cable |
Protection(overvoltage) | 30V maximum,limited to 1 hour per dayfrequency |
Transistor Output Characteristics | 4 Point |
Rated Voltage | 24 VDC |
Voltage Range | 19.2~28.8VDC |
Rated Current | 0.5A |
Current/group | 0.5A*Output point of each group |
Voltage Drop | Maximum 1VDC |
Leakage Current When Turned Off | <5μA |
Maximum Power of Incandescent Lamp | 2.4W |
Derating | None |
Start Time | Maximum 34μs |
Turn-off Time | Maximum 250μs |
Maximum Output Frequency | 1KHz |
Short Circuit Protection | Available |
Peak Short-circuit Output Curent | 1.3A |
Self-recovery After Short Circuit or Overload | Per10ms |
Clamping Voltage | Maximum39VDC,±1V |
Isolation | 500V AC between output and internal logic |
Type of Electrical Channel | Unshielded |
Cable Length | Unshielded 50m |